  Author£ºskydive¡¡ 2009-7-13 ÏÂÎç 02:53:31¡¡¡¡ Reply
Problem : No AC output on start-up. Symptoms : Generator starts. Voltmeter indicates +200 VAC. Oil pressure warning light illuminates. Relay on the Oil Pressure warning light board clicks. VAC output drops to zero. Timescale of +/- 1 second. History : Possible back-feed from mains AC to generator. Replaced the regulator box. Tested and disconnected oil pressure switch. Could it be possible short on the windings producing over-charge?
reply£ºKDE6500E no AC outp
Need to check the windings. Start by removing the exhaust system Check the resistance across the brushes. It should be 30 - 40 ohms. This must be in spec. Then if you are competent to do so Connect 12V+ to the LEFT HAND BRUSH TERMINAL Connect 12- to the RIGHT HAND BRUSH TERMINAL power the machine up and it May show 140 - 160V on the voltmeter. Check across the 2 yellow wires going into the alternator they should be about 65 - 80 V ac Check the 2 blue wires they should be 10 - 18V ac Any failure in any of these tests indicates a blown alternator. If all ok it SHOULD be the AVR Good Luck